Dimensions
Product Net Width: 278 mm
Product Net Height: 363.5 mm
Product Net Depth / Length: 271 mm
Product Net Weight: 18 kg
Container Information
Package Level 1 Units: box 1 piece
Package Level 1 Width: 270 mm
Package Level 1 Height: 350 mm
Package Level 1 Depth / Length: 330 mm
Package Level 1 Gross Weight: 20 kg
Package Level 1 EAN: 8015644760014
Additional Information
Product Main Type: SACE Emax 2
Product Name: Air Circuit Breaker
Product Type: Air Circuit Breaker
Version: W
CAD Dimensional Drawing: E1.2 III W
Technical
Current Type: AC
Electrical Durability:
Ue =< 440 V 8000 cycle
Ue = 500 … 690 V 8000 cycle
30 cycles per hour
Mechanical Durability:
20000 cycle
60 cycles per hour
Number of Poles: 3P
Power Loss: 156 W
Rated Current (In): 1000 A
Rated Impulse Withstand Voltage (Uimp): acc. to IEC 60947-2 12 kV
Rated Insulation Voltage (Ui): AC 1000 V
Rated Operational Voltage: 690 V AC
Rated Service Short-Circuit Breaking Capacity (Ics):
(220 V AC) 66 kA
(230 V AC) 66 kA
(380 V AC) 66 kA
(400 V AC) 50 kA
(415 V AC) 50 kA
(440 V AC) 50 kA
(500 V AC) 50 kA
(660 V AC) 50 kA
(690 V AC) 50 kA
Rated Service Short-Circuit Breaking Capacity, in % of Icu (Ics): 100 %
Rated Short-time Withstand Current Low Voltage (Icw):
for 1 s 50 kA
for 3 s 30 kA
Rated Ultimate Short-Circuit Breaking Capacity (Icu):
(400 V AC) 66 kA
(415 V AC) 66 kA
(440 V AC) 66 kA
(500 V AC) 50 kA
(525 V AC) 50 kA
(690 V AC) 50 kA
Rated Uninterrupted Current (Iu): 1000 A
Rated Voltage (Ur): 690 V
Release: Ekip Dip LI
Release Type: EL
Short-Circuit Performance Level: N
Standards: IEC
Sub-type: E1.2
Suitable for IT Networks: Yes, 690V
Reviews
There are no reviews yet.